Three Phase AC Capacitors |



|
Brackets can be modified upon request.
The weight does not include the optional cover with dimensions 470 x 600 x (B+340) mm and which weighs 16 kg. |
|
Style |
Power |
Current |
Dimensions |
Weight |
|
|
(kVAr) |
(A) |
A (mm) |
B (mm) |
(kg) |
|
|
|
|
|
|
|
|
|
Un: = 3.0 kV |
|
|
|
||
|
5K00 |
50 |
9.6 |
250 |
280 |
16 |
|
5K00 |
75 |
14.4 |
310 |
340 |
20 |
|
5K00 |
100 |
19.2 |
370 |
400 |
24 |
|
5K00 |
150 |
28.9 |
510 |
540 |
30 |
|
5K00 |
200 |
38.5 |
630 |
660 |
37 |
|
|
|
|
|
|
|
|
Un: = 3.3 kV |
|
|
|
||
|
5K30 |
50 |
8.4 |
240 |
270 |
16 |
|
5K30 |
75 |
13.1 |
300 |
330 |
20 |
|
5K30 |
100 |
17.5 |
360 |
390 |
24 |
|
5K30 |
150 |
26.4 |
480 |
510 |
30 |
|
5K30 |
200 |
35.0 |
610 |
640 |
37 |
|
|
|
|
|
|
|
|
Un: = 6.3 kV |
|
|
|
||
|
5N30 |
50 |
4.6 |
250 |
280 |
16 |
|
5N30 |
75 |
6.9 |
310 |
340 |
20 |
|
5N30 |
100 |
9.2 |
370 |
400 |
24 |
|
5N30 |
150 |
13.7 |
490 |
520 |
30 |
|
5N30 |
200 |
18.4 |
600 |
630 |
37 |
|
5N30 |
250 |
22.9 |
740 |
770 |
42 |
|
5N30 |
300 |
27.5 |
870 |
900 |
55 |
|
Bushing Height |
|
|
BIL |
K |
|
(kV) |
(mm) |
|
60 |
152 |
|
75 |
185 |
|
95 |
225 |
|
Permitted Overvoltage |
|
|
Condition |
Working |
|
Voltage |
|
|
8 hours / day |
1.10 x Un |
|
30 min. / day |
1.15 x Un |
|
5 min. 200 times |
1.20 x Un |
|
1 min. 200 times |
1.25 x Un |
|
Temperature |
Ambient Air Temperature |
|||
|
Symbol |
Meaning |
Max. |
Highest Mean Over Any Period of |
|
|
24 hours |
1 year |
|||
|
-25/C |
-25/+50°C |
50°C |
40°C |
30°C |